草久久免费视频_日韩在线一区二区三区人_nxgx欧美_伊人久久大香线蕉aⅴ色_日本一二三区免费_久久久噜噜噜久久中文福利

Product Center

Product Classification
ZM-3D Series Multi-function monitoring instrument

Print current page

Product Description

  • brief introduction
  • technical parameter
  • Product size

Application

Multi-functional monitor and control meter is a high performance intelligent instrument, with such functions of measuring power parameters and harmonic waves at real time, measuring positive and negative active / reactive energy, measuring energy at separate time zone, reading energy at fixed time zone, analyzing electric quality, displaying wave at real time, recording events, demands and etc. also it provides various input and output interfaces for monitoring and control on ?site, ?and ?integrated ?with ?RS-485 ?port, cooperated with different intelligent distribution system and administration system, share the parameters and data of system. This meter has very highperformance and price index, completely replace power transmitter, measuring instruments, energy meters and associated parts, widely used in energy administration system, power monitoring system, mineral enterprises, public facilities, smart buildings, switchgears and etc intelligent power system.


Conforming to standards

1. GB/T 22264.1-2008:Mounted digital display electric measuring instruments-Part1: Definitions and general requirements

2. GB/T 22264.7-2008:Mounted digital display electric measuring instruments-Part 7: Special requirements for??multi-funcational meters

3. GB/T 22264.8-2008:Mounted digital display electric measuring instruments-Part8: Recommended test methods

4. GB/T 17215.322-2008: AC electric measurement devices ?Special requirements Part 22: Static active energy??meter (class 0.2S and 0.5S)

5. GB/T 17215.323-2008: AC electric measurement devices ?Special requirements Part 23: Static reactive energy meter (Class 2 and 3)

6. Multi-functional energy meter

7. Detector for electric fire protection

8. Code for Fire Protection Design of Tall Civil Buildings

9. Code for Low voltage distribution design

10. Code for living building design

11. Installation and operation of residual current tripping protective device

12. Code of Design on Building Fire Prevention

Code and implication



Technical index

Accuracy of measurement

Voltage level 0.5

Current level 0.5

Active power 0.5

Reactive power level 0.5

Frequency ±0.02Hz

Active electric energy class 0.5S or class 0.2S

Reactive energy grade 1 or grade 2

Power factor 0.5


Signal input

◆Connection mode of four phase three wire, ?three phase , three line

◆Rated voltage AC 57.7V,AC 100V,AC 220V,AC 380V

◆Rated current AC 1A, ?AC 5A

◆Overload voltage:1.2 times(Continued), 2 times/second(instantaneous)

current:1.2 times(Continued), 10 times/5 second(instantaneous)

◆Power consumption voltage:<1VA/, current:<0.4VA/phase

◆Impedance voltage:>300mKΩ, current:<20mΩ

◆The frequency 45~65Hz

Auxiliary power supply

◆Working range ?AC/DC 80V~270V

◆Power consumption<4VA


Function module

◆Communication interface 1 way RS-485 communication, Modbus-RTU protocol baud r ate:1200~9600bps, the default ?2400bps

◆Switch input: support 4 stem node input

◆The switch output: support 3 relay output, capacity: AC 250V/5A, DC 30V/5A

◆Transmission output: support 3 analog output: 0/4~20mA or 0~5/10V

◆Electirc energy pulse output support 2 electric energy pulse output, constant: 8000imp/KWh(kvarh)


Environment

◆Working temperature: -10℃~+55℃

◆Storage temperature: -25℃~+70℃

◆Relative humidity is less than 93%, no corrosive gas

◆Elevation≤2500m


Safety

◆Insulation resistance>100MΩ

◆AC withstand voltage AC 2KV


Electromagnetic compatibility

◆ESD level 4

◆Electrical fast transient burst level 4

◆Surge(impact) level 4


Performance Characteristics

◆High precision measurement of three-phase voltage, active ?power, reactive power, apparent power, power factor, frequency of electric parameters

◆Forward and reverse active /reactive energy meas-urement

◆Division of electric energy metering, time-sharing/power ?timing meter reading

◆Measurement of three-phase voltage, three-phase current total harmonic distortion (THD), 2-31 odd harmonic component

◆ To provide a nixie tube or liquid crystal display, local data query

◆Menu button intuitive, simple operation

◆Current, votlage gain Programmable

◆Provide multiple circuit leakage current monitoring

◆Provide mulitple loop control nodes, can be used for the alarm, trip control

◆Support for fire control, remote cut off the fault circuit

◆Support for RS-485 communication, Modbus -RTU protocol

◆Support for switching input, output, analog quantity transmitting output

◆Convenient installation, wiring is simple, small eng-ineering quantity

◆A wide range of AC/DC power supply: AC/DC80V-270V

◆To be completed by SCADA, PLC in a variety of communications software networking.



External And Installation Size


Frame size(mm) : 120×120;80×80;96×48;
96×96;72×72;48×48;

Hole size(mm) : 111×111;76×76;92×45;
92×92;68×68;45×45;

主站蜘蛛池模板: 在线精品一区二区 | 曰批全过程免费视频在线观看网站 | 日韩欧美高清 | 午夜福利在线永久视频 | 国产激情精品久久久第一区二区 | 亚洲高清免费 | 人妻聚色窝窝人体WWW一区 | 欧美日韩在线观看一区二区 | 久久婷婷五月综合色99啪 | 精品国产一区二区三区国产区 | 国产在线看片无码人精品 | 性爱国产精品福利 | 国产精品久久久久久久久福交 | 亚洲欧美日韩中文字幕一区二区三区 | eeuss第一页| 国产一级做a爰片久久真人片男 | 香蕉久久久久久AV综合网成人 | 九九午夜 | 四虎成人免费视频在线播放 | JAPANESEHD无码中文字幕 | 丁香激情综合色伊人久久 | 欧洲女人牲交性开放视频 | 久久香蕉影院 | a在线视频观看 | 日韩三级一区二区 | 国产成人综合久久免费导航 | 欧美群伦性艳史黄94 | 日美一级毛片 | 中文字幕丰满人伦在线 | 亚洲人成人无码.WWW石榴 | 国产一区免费播放 | 91精品国产一区二区三区四区在线 | 国产在线拍偷自揄拍视频 | 亚洲一区二区中文播放av | 亚洲熟妇无码AV在线播放 | 亚洲欧洲久久av | 少妇人体色www网站 日韩精品一区二区三区swag | 国产骚妻 | 又粗又黄又爽视频免费看 | 亚洲AV成人WWW永久无码精品 | 最近2019年日本中文免费字幕 |